4. FC 300 Selection
The frequency converter constantly checks for critical levels of internal temperature, load current, high voltage on the intermediate circuit and
low motor speeds. As a response to a critical level, the frequency converter can adjust the switching frequency and/ or change the switching
pattern in order to ensure the performance of the drive.
Digital inputs:
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
4
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Pulse frequency range
(Duty cycle) Min. pulse width
Input resistance, R
i
Safe stop Terminal 37
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Nominal input current at 24 V
Nominal input current at 20 V
Input capacitance
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
2) Except safe stop input Terminal 37.
3) Terminal 37 is only available in FC 302 and FC 301 A1 with Safe Stop. It can only be used as safe stop input. Terminal 37 is suitable for category 3
installations according to EN 954-1 (safe stop according to category 0 EN 60204-1) as required by the EU Machinery Directive 98/37/EC. Terminal 37
and the Safe Stop function are designed in conformance with EN 60204-1, EN 50178, EN 61800-2, EN 61800-3, and EN 954-1. For correct and safe use
of the Safe Stop function follow the related information and instructions in the Design Guide.
4) FC 302 only.
Analog inputs:
Number of analog inputs
Terminal number
Modes
Mode select
Voltage mode
Voltage level
Input resistance, R
i
Max. voltage
Current mode
Current level
Input resistance, R
i
Max. current
Resolution for analog inputs
Accuracy of analog inputs
Bandwidth
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
66
2)
2)
3)
(Terminal 37 is fixed PNP logic):
MG.33.BA.02 - VLT
FC 301: 0 to + 10/ FC 302: -10 to +10 V (scaleable)
®
is a registered Danfoss trademark
FC 300 Design Guide
FC 301: 4 (5) / FC 302: 4 (6)
1)
4)
18, 19, 27
, 29
, 32, 33,
PNP or NPN
0 - 24 V DC
< 5 V DC
> 10 V DC
> 19 V DC
< 14 V DC
28 V DC
0 - 110 kHz
4.5 ms
approx. 4 kΩ
0 - 24 V DC
< 4 V DC
>20 V DC
50 mA rms
60 mA rms
400 nF
2
53, 54
Voltage or current
Switch S201 and switch S202
Switch S201/switch S202 = OFF (U)
approx. 10 kΩ
± 20 V
Switch S201/switch S202 = ON (I)
0/4 to 20 mA (scaleable)
approx. 200 Ω
30 mA
10 bit (+ sign)
Max. error 0.5% of full scale
FC 301: 20 Hz/ FC 302: 100 Hz