9. RS-485 Installation and Set-up
9.5.2. Reading a parameter value
Read the value in par. 3-41
PKE = 1155 Hex - Read parameter value in par. 3-41
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 0000 Hex
If the value in par. 3-41
slave to the master will be:
NB!
3E8 Hex corresponds to 1000 decimal. The conversion index for par. 3-41 is -2, i.e. 0.01.
9

9.6. Danfoss FC Control Profile

9.6.1. Control Word According to FC Profile(Par. 8-10 = FC profile)
172
Ramp 1 Up Time.
Ramp 1 Up Time
Ramp 1 Up Time
is 10 s, the response from the
MG.33.BA.02 - VLT
®
is a registered Danfoss trademark
FC 300 Design Guide