Bit 15 = '0': No reversing. Bit 15 = '1': Reversing. In the default setting, reversing is set to digital in par. 8-54
only when Ser. communication, Logic or or Logic and is selected.
9.6.2. Status Word According to FC Profile (STW) (Par. 8-10 = FC profile)
Bit
Bit = 0
00
Control not ready
01
Drive not ready
02
Coasting
03
No error
04
No error
05
Reserved
06
No error
07
No warning
08
Speed ≠ reference
09
Local operation
10
Out of frequency limit
11
No operation
12
Drive OK
13
Voltage OK
14
Torque OK
15
Timer OK
Explanation of the Status Bits
Bit 00, Control not ready/ready:
Bit 00 = '0': The frequency converter trips. Bit 00 = '1': The frequency converter controls are ready but the power component does not necessarily receive
any power supply (in case of external 24 V supply to controls).
Bit 01, Drive ready:
Bit 01 = '1': The frequency converter is ready for operation but the coasting command is active via the digital inputs or via serial communication.
Bit 02, Coasting stop:
Bit 02 = '0': The frequency converter releases the motor. Bit 02 = '1': The frequency converter starts the motor with a start command.
Bit 03, No error/trip:
Bit 03 = '0' : The frequency converter is not in fault mode. Bit 03 = '1': The frequency converter trips. To re-establish operation, enter [Reset].
Bit 13
0
1
0
1
Multi Set-Ups
is selected in par. 0-10
MG.33.BA.02 - VLT
®
is a registered Danfoss trademark
9. RS-485 Installation and Set-up
NB!
Make a selection in par. 8-55
how Bit 13/14 gates with the corresponding function