8. Options and Accessories
Cable strips for fastening cables to relay module
The relay option does not support FC 302 frequency converters manufactured before week 50/2004.
Min. software version: 2.03 (par. 15-43).
1)
IMPORTANT! The label MUST be placed on the LCP frame as shown (UL approved).
8
Warning Dual supply
How to add the MCB 105 option:
The power to the frequency converter must be disconnected.
The power to the live part connections on relay terminals must be disconnected.
Remove the LCP, the terminal cover and the LCP fixture from the FC 30x.
Fit the MCB 105 option in slot B.
Connect the control cables and fasten the cables with the enclosed cable strips.
Make sure the length of the stripped wire is correct (see the following drawing).
Do not mix live parts (high voltage) with control signals (PELV).
Fit the enlarged LCP fixture and enlarged terminal cover.
Replace the LCP.
Connect power to the frequency converter.
Select the relay functions in par. 5-40 [6-8], 5-41 [6-8] and 5-42 [6-8].
NB!
Array [6] is relay 7, array [7] is relay 8, and array [8] is relay 9
158
A2-A3-B3
MG.33.BA.02 - VLT
A5-B1-B2-B4-C1-C2-C3-C4
®
is a registered Danfoss trademark
FC 300 Design Guide