FC 300 Design Guide
Illustration 6.15: Cable entry seen from the bottom of the fre-
quency converter - Enclosure E1.
The bottom plate of the E1 enclosure can be mounted from either in- or outside of the enclosure, allowing flexibility in the installation process, i.e. if
mounted from the bottom the glands and cables can be mounted before the frequency converter is placed on the pedestal.
Illustration 6.16: Mounting of bottom plate, E1 enclosure.
6.3.5. IP21 Drip shield installation (D1 and D2 enclosure)
To comply with the IP21 rating, a separate drip shield is to be
installed as explained below:
Remove the two front screws
Insert the drip shield and replace screws
Torque the screws to 5,6 Nm (50 in-lbs)
Illustration 6.17: Drip shield installation.
MG.33.BA.02 - VLT
®
is a registered Danfoss trademark
6. How to Install
6
105