8.2.2. Digital inputs - Terminal X30/1-4
Digital input:
Number of digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP (GND = 0 V)
Voltage level, logic'1' PNP (GND = 0 V)
Voltage level, logic '0' NPN (GND = 24V)
Voltage level, logic '1' NPN (GND = 24 V)
Maximum voltage on input
Pulse frequency range
Duty cycle, min. pulse width
Input impedance
8.2.3. Analog inputs - Terminal X30/11, 12:
Analog input:
Number of analog inputs
Terminal number
Modes
Voltage level
Input impedance
Max. voltage
Resolution for analog inputs
Accuracy of analog inputs
Bandwidth
8.2.4. Digital outputs - Terminal X30/6, 7:
Digital output:
Number of digital outputs
Terminal number
Voltage level at digital/frequency output
Max. output current
Max. load
Max. capacitive load
Minimum output frequency
Maximum output frequency
Accuracy of frequency output
8.2.5. Analog output - Terminal X30/8:
Analog output:
Number of analog outputs
Terminal number
Current range at analog output
Max. load GND - analog output
Accuracy on analog output
Resolution on analog output
MG.33.BA.02 - VLT
®
is a registered Danfoss trademark
8. Options and Accessories
3
X30.2, X30.3, X30.4
PNP or NPN
0 - 24 V DC
< 5 V DC
> 10 V DC
< 14 V DC
> 19 V DC
28 V continous
0 - 110 kHz
4.5 ms
> 2 kΩ
2
X30.11, X30.12
Voltage
0 - 10 V
> 10 kΩ
20 V
10 bit (+ sign)
Max. error 0.5% of full scale
FC 301: 20 Hz/ FC 302: 100 Hz
2
X30.6, X30.7
0 - 24 V
40 mA
≥ 600 Ω
< 10 nF
0 Hz
≤ 32 kHz
Max. error: 0.1 % of full scale
1
X30.8
0 - 20 mA
500 Ω
Max. error: 0.5 % of full scale
12 bit
8
153