Module Reaction - Burkert 8647 AirLINE SP Quick Start Manual

Valve block with interface to the distributed i/o system
Table of Contents

Advertisement

Troubleshooting

13.2 Module reaction

13.2.1 LED display PSU-L-...connection units
malfunction
possible cause
LED PWR
No or insufficient load
OK off
voltage (see chapter
"14 Technical data")
Module-internal fuse
has tripped or other
module defect
13.2.2 LED display PQ modules and PSU-...-PS
connection units
malfunction
possible cause
LED DIAG off Backplane
bus supply of
ET 200SP / SP HA
faulty
LED DIAG
Module not ready
flashes green
for operation (not
parameterized)
LED DIAG
Module is param-
flashes red
eterized, module
sends diagnostics
Type 8647
corrective action
Check the electrical
connection
Ensure correct load
voltage
Replace connection
unit (please contact
the Bürkert Service)
corrective action
Check operating voltage
of the interface module
Check correct
arrangement of
ET 200SP / SP HA
modules and valve block
Carry out valid
parameterization via the
configuration tool
Eliminate cause for
diagnostics
malfunction
possible cause
LED PWR
No or insufficient
off (only PQ
load voltage
modules)
Module-internal fuse
has tripped or other
module defect
Load voltage supply
at EVS connection
interrupted (only
modules with EVS
connection)
LED Pressure
Parameterized
lights up
warning limit
undercut
orange
("Warn", only
Parameterized
PSU-...-PS
warning limit
connection
exceeded
units)
LED Pressure
Parameterized error
lights up red
limit undercut
("Error", only
PSU-...-PS
Parameterized error
connection
limit exceeded
units)
english
corrective action
Check the electrical
connection
Ensure correct load
voltage
Replace electronics
module (please contact
the Bürkert Service)
Check wiring of EVS
connection
Increase pressure
or
Set a lower warning limit
Reduce pressure
or
Set higher warning limit
Increase pressure
or
Set lower error limit
Reduce pressure
or
Set higher error limit
35