→ Tighten the fastening screws clockwise (tightening torque
approx. 1.8 Nm).
→ Attach the BaseUnits of SIMATIC ET 200SP / SP HA to the
standard rail on the left of the valve block according to the
instructions provided by the manufacturer. Push the BaseUnits
to the valve block until the catch hook audibly engages. To
ensure the plug-in connections are connected properly, make
sure the BaseUnits are firmly on the valve block along the
entire length.
→ Preferably install a light-colored BaseUnit (type code BU...D
or BU...D/T) immediately to the left of the valve block
(required in combination with SIMATIC ET 200SP HA).
→ To the right of the valve block, install either the server
module or further BaseUnits of SIMATIC ET 200SP (only
permissible with SIMATIC ET 200SP stations, not with
SIMATIC ET 200SP HA stations). If further BaseUnits are to
be installed, the first BaseUnit after the valve block must be
a light-colored BaseUnit (BU...D or BU...D/T) to supply the
necessary load voltage.
7.3
Installing the valve block on the base
of the control cabinet (with AirLINE
Quick)
When using the control cabinet base adaption "AirLINE Quick",
the device is mounted to the control cabinet base via a solid
metal plate. In this case, the device supports the standard rail
(incl. the modules of SIMATIC ET 200SP mounted thereon) rather
than the other way round.
18
english
Type 8647
Installation
noTe
▶ Observe the specifications in the configuration file for the
installation sequence.
▶ Ground the standard rail with low impedance to guarantee
the best possible EMC protection.
When configuring the modules of SIMATIC ET 200SP,
observe that the permissible projection of the standard
rail is limited to 10 cm on both sides of the valve block.
Only short BaseUnits can be used.
Combination of AirLINE Quick with
SIMATIC ET 200SP HA is not possible due to the design.
≤ 10 cm
Valve block
AirLINE Quick
Fig. 9:
Installation position in the control cabinet when using AirLINE
Quick
≤ 10 cm
Standard rail
Base of control cabinet