Application Planning
6.3.2 Valve block in combination with
SIMATIC ET 200SP
Number of
64 I/O modules / connection units / elec-
modules
tronic basic modules in complete valve island
(Siemens SIMATIC ET 200SP + AirLINE SP
Type 8647 valve blocks)
Valve blocks
Several possible in one station as long as the
permissible width is adhered to.
Position on
Valve blocks can be positioned as required.
station
Further SIMATIC ET 200SP I/O modules can be
mounted to the right of a valve block.
AirLINE
It is possible to use the "AirLINE Quick" control
Quick
cabinet base adaptation, but restrictions
must be observed with regard to the applied
BaseUnits and the number of SIMATIC ET
200SP modules (for details see section "7.3").
Width
Maximum 975 mm* (incl. all Siemens modules,
but without interface module)
Further restrictions may result from the installation position, the
applied interface module and performance considerations (see
also the SIMATIC ET 200SP system manual).
*)
Depending on the design of the valve block(s), 25 mm must be
deducted from the specification of ET 200SP (1000 mm permissible
Type 8647
6.3.3 Valve block in combination with
SIMATIC ET 200SP HA
Number of
56 I/O modules / connection units / elec-
modules
tronic basic modules in complete valve island
(Siemens SIMATIC ET 200SP HA + valve block
AirLINE SP Type 8647)
Valve blocks
Only one valve block per station possible.
Position on
The valve block can only be mounted to the
station
right of a SIMATIC ET 200SP HA station.
Further SIMATIC ET 200SP I/O modules cannot
be mounted to the right of the valve block.
AirLINE
It is not possible to use the "AirLINE Quick"
Quick
control cabinet base adaptation in combination
with SIMATIC ET 200SP HA.
Width
Maximum 1240 mm* (incl. all Siemens modules,
but without interface module(s))
Further restrictions may result from the installation position, the
applied interface module and performance considerations (see
also the SIMATIC ET 200SP HA system manual).
*)
Depending on the design of the valve block, 20 mm must be
deducted from the specification of ET 200SP HA (1260 mm
).
permissible
).
english
15