Technical data

14.3 Pneumatic data

Control medium
Dry compressed air oiled or unoiled,
neutral gases
ISO 8573-1: 2010, class 7.4.4*
Compressed air
quality as per
Temperature range
–10...+50 °C (when using valve type
0460: +5...+50 °C)
of the medium
Pressure range
Vacuum up to 10 bar (when using valve
type 0460: 2...7 bar)
Air flow rate (QNn value, for further details see data sheet):
300 l/min (when using pneumatic base
Monostable
valves (Type
modules with "P shutoff", the flow rate is
reduced to approx. 60%)
6524 and
Type 6525)
200 l/min
Impulse valves
(Type 0460)
Connections:
G1/4" thread (other connections possible
Compressed
air supply and
via adapter)
exhaust air
M5
Auxiliary control
air or pilot
control exhaust
air
Type 8647
Plug-in coupling Ø 6 mm or Ø D1/4
Working
connections
or
M7 threaded bushing
Pressure sensor (connection units PSU-...-PS):
Measuring range
0...10 bar (relative to environment)
Overpressure
14 bar (with higher pressures, irreversible
impairment of the measuring precision)
resistance
Precision
0.2 bar
Measurement
> 10/second
rate
Filtering
Median filter (additional filtering of the
measured value at the control is recom-
mended in case of highly variable media
consumption)
*
To prevent the expanded compressed air freezing, its pressure dew
point must be at least 10 K less than the medium temperature.
english