General Technical Data - Burkert 8647 AirLINE SP Quick Start Manual

Valve block with interface to the distributed i/o system
Table of Contents

Advertisement

simaTic eT 200sp ha
System manual:
https://support.industry.siemens.com/cs/ww/en/
view/109761547
Manuals:
https://support.industry.siemens.com/cs/ww/en/ps/24728/man
The complete system must be installed in a suitable control
cabinet or in a suitable housing. The control cabinet requirements
correspond to those of the Siemens distributed I/O system
"SIMATIC ET 200SP" or "SIMATIC ET 200SP HA", but at least to
degree of protection IP54.
Type of condition
permissible range
Ambient
0...+55 °C
temperature
Valve blocks with valve Type 0460:
0...+50 °C
Humidity
75% on average, 85% occasionally,
condensation not permitted
Air pressure
80 kPa to 106 kPa
(When used at heights above 2000 m
mean sea level, the power supply must
take place via a SELV/PELV power supply
unit approved for use at this height.)
Media
Neutral gaseous media, oiled or unoiled
Max. particle size 5 µm
Altitude
Restricted to max. 2000 m above sea
level for UL approved versions
38
english
Type 8647
Technical data

14.2 general technical data

Dimensions
max. 858 mm x 142 mm x 78 mm
(depending on the extension, valve
variants, module variants)
Weight
max. 10 kg (depending on the extension)
Material of the
PA, PC (valves: PA / PPS / Al)
housing
Material of the seal NBR
Degree of pro-
IP20
tection (according
IP65 in closed control cabinets
to EN 60529)
verified by Bürkert,
not evaluated
by UL
Protection class
3
(according to DIN
Installation on standard rail with FE func-
EN 61140, VDE
tional ground required
0140)