REG615
Application Manual
T1PTTR1_BLK_CLOSE
GUID-A05280B3-2B7C-4931-9FE2-0695789A3340 V2 EN
Figure 52:
Circuit breaker 1 close blocking logic
The configuration includes logic for generating circuit breaker external closing and
opening command with the relay in local or remote mode.
Check the logic for the external circuit breaker closing command and
modify it according to the application.
Connect additional signals for opening and closing of circuit breaker
in local or remote mode, if applicable for the configuration.
B1
CONTROL_LOCAL
B2
FALSE
B1
CONTROL_REMOTE
B2
FALSE
GUID-6B6BCEDB-7309-4BED-BEE2-66CCC4FDDB61 V2 EN
Figure 53:
External closing command for circuit breaker 1
B1
CONTROL_LOCAL
B2
FALSE
B1
CONTROL_REMOTE
B2
FALSE
GUID-8AB476A5-0AA2-4533-B119-A69EDFA5FFB3 V2 EN
Figure 54:
External opening command for circuit breaker 1

Functional diagram for measurement functions

The phase current inputs to the relay are measured by the three-phase current
measurement function CMMXU1. The current input is connected to the X120 card in
the back panel. The sequence current measurement CSMSQI1 measures the sequence
current and the residual current measurement RESCMMXU1 measures the residual
current.
REG615 standard configurations
OR6
B1
B2
B3
B4
B5
B6
AND
O
B1
B2
AND
O
AND
O
B1
B2
AND
O
Section 3
O
CBXCBR1_BLK_CLOSE
OR
O
CBXCBR1_AU_CLOSE
OR
O
CBXCBR1_AU_OPEN
59