Functional Diagrams - ABB RELION 615 Series Applications Manual

Generator and interconnection protection
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MRS758272 B
3.5.3
REG615
Application Manual
Channel
ID text
56
X130BI1 - Ext trip1
57
X130BI2 - Ext trip2
58
X130BI4 - Field excitation open
59
X110BI7 - CB closed
60
X110BI8 - CB open
61
ARCSARC1 - ARC flt det
ARCSARC2 - ARC flt det
ARCSARC3 - ARC flt det
62
ARCSARC1 - operate
63
ARCSARC2 - operate
64
ARCSARC3 - operate

Functional diagrams

The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements.
The analog channels have fixed connections to the different function blocks inside the
protection relay's standard configuration. However, the 12 analog channels available
for the disturbance recorder function are freely selectable as a part of the disturbance
recorder's parameter settings.
The analog channels are assigned to different functions. The phase currents to the
protection relay are fed from a current transformer. The common signal marked with
3I represents the three phase currents of the neutral side of the generator and 3IB
represents the three phase currents of the terminal side of the generator. It is assumed
that the core balance CT is provided both on line and neutral side of the generator and
are connected such that the differential residual current is fed to the protection relay.
The terminal side phase voltages to the protection relay are fed from a voltage
transformer. The residual voltage to the protection relay is fed from either residually
connected VTs, an open delta connected VT or internally calculated.
The protection relay offers six different setting groups which can be set based on
individual needs. Each group can be activated or deactivated using the setting group
settings available in the protection relay.
Depending on the communication protocol the required function block needs to be
instantiated in the configuration. The Application Configuration tool also includes
fixed Boolean signals TRUE and FALSE which can be used according to the
application needs.
REG615 standard configurations
Section 3
Level trigger mode
Positive or Rising
Positive or Rising
Positive or Rising
Level trigger off
Level trigger off
Level trigger off
Positive or Rising
Positive or Rising
Positive or Rising