ABB RELION 615 Series Applications Manual page 51

Generator and interconnection protection
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MRS758272 B
B1
DPHHPDOC1_OPERATE
B2
DPHLPDOC1_OPERATE
B3
PHIPTOC1_OPERATE
B4
DPHLPDOC2_OPERATE
B5
EFHPTOC1_OPERATE
B6
B1
ARCSARC1_OPERATE
B2
ARCSARC2_OPERATE
B3
ARCSARC3_OPERATE
B4
B5
B6
GUID-C53EDBAE-9237-4FF3-A053-FE0647781159 V2 EN
Figure 21:
Circuit breaker failure protection function
REG615
Application Manual
The circuit breaker failure protection function has two operating outputs: TRRET and
TRBU. The TRRET operating output is used for retripping its own breaker through
TRPPTRC2_TRIP. The output TRBU gives a backup trip to the breaker feeding
upstream. For this purpose, the TRBU operating output signal is connected to the
binary output X100:PO2.
OR6
B1
O
B2
B3
B4
B5
B6
X110_BI7_CB_CLOSED
OR6
O
Three arc protection ARCSARC1...3 stages are included as an optional function. The
arc protection offers individual function blocks for three arc sensors that can be
connected to the relay. Each arc protection function block has two different operation
modes, that is, with or without the phase and residual current check.
The operating signals from ARCSARC1...3 are connected to both trip logic
TRPPTRC1 and TRPPTRC2. If the relay has been ordered with high speed binary
outputs, the individual operating signals from ARCSARC1...3 are connected to
dedicated trip logic TRPPTRC3...5. The outputs of TRPPTRC3...5 are available at
high speed outputs X110:HSO1, X110:HSO2 and X110:HSO3 respectively.
REG615 standard configurations
CCBRBRF1(3I>/Io
OR6
BLOCK
O
START
POSCLOSE
CB_FAULT
Section 3
CB_FAULT_AL
TRBU
CCBRBRF1_TRBU
TRRET
CCBRBRF1_TRRET
45