Section 3 Reg615 Standard Configurations; Standard Configurations - ABB RELION 615 Series Applications Manual

Generator and interconnection protection
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MRS758272 B
Section 3
3.1
Table 10:
Supported functions
Function
Protection
Three-phase non-directional overcurrent protection, low stage
Three-phase non-directional overcurrent protection, high stage
Three-phase non-directional overcurrent protection, instantaneous
stage
Three-phase directional overcurrent protection, low stage
Three-phase directional overcurrent protection, high stage
Three-phase voltage-dependent overcurrent protection
Non-directional earth-fault protection, high stage
Directional earth-fault protection, low stage
Directional earth-fault protection, high stage
Transient/intermittent earth-fault protection
Negative-sequence overcurrent protection
Negative-sequence overcurrent protection for machines
Residual overvoltage protection
Table continues on next page
REG615
Application Manual
REG615 standard configurations

Standard configurations

REG615 is available with three alternative standard configurations. The standard
signal configuration can be altered by means of the signal matrix or the graphical
application functionality of the Protection and Control IED Manager PCM600.
Further, the application configuration functionality of PCM600 supports the creation
of multi-layer logic functions using various logical elements, including timers and
flip-flops. By combining protection functions with logic function blocks, the relay
configuration can be adapted to user-specific application requirements.
The protection relay is delivered from the factory with default connections described
in the functional diagrams for binary inputs, binary outputs, function-to-function
connections and alarm LEDs. Some of the supported functions in REG615 must be
added with the Application Configuration tool to be available in the Signal Matrix tool
and in the relay. The positive measuring direction of directional protection functions
is towards the busbar.
Table 9:
Standard configurations
Description
Interconnection protection for distributed power generation
Generator protection with 100% stator earth-fault protection
Generator protection with generator differential and directional overcurrent protection and
synchro-check
REG615 standard configurations
IEC 61850
A
PHLPTOC
PHHPTOC
PHIPTOC
1
DPHLPDOC
2
DPHHPDOC
1
PHPVOC
EFHPTOC
1
DEFLPDEF
2
DEFHPDEF
1
INTRPTEF
1)
1
NSPTOC
2
MNSPTOC
ROVPTOV
2
Section 3
Std. conf.
C
D
1
1
1
1
1
1
TR
1
TR
1
1
1
1
1
2
2
1
1
2
2
2
2
A
C
D
31