Section 5
Protection relay's physical connections
5.1.1.4
5.1.2
5.1.3
138
Table 31:
Reference voltage input for SECRSYN1 included in configurations A and D
Terminal
X130:9-10
Residual voltage
Table 32:
Additional residual voltage input included in configurations A, C and D
Terminal
X130:9-10
X130:17-18
1) Used only for H3EFPSEF1 in configuration C
Auxiliary supply voltage input
The auxiliary voltage of the protection relay is connected to terminals X100:1-2. At
DC supply, the positive lead is connected to terminal X100:1. The permitted auxiliary
voltage range (AC/DC or DC) is marked on the top of the LHMI of the protection
relay.
Table 33:
Auxiliary voltage supply
Terminal
X100:1
X100:2
Binary inputs
The binary inputs can be used, for example, to generate a blocking signal, to unlatch
output contacts, to trigger the disturbance recorder or for remote control of protection
relay's settings.
Binary inputs of slot X110 are available with configurations A, C and D.
Table 34:
Binary input terminals X110:1-13 with BIO0005 module
Terminal
X110:1
X110:2
X110:3
X110:4
X110:5
X110:6
X110:6
X110:7
Table continues on next page
Description
U12B
Description
1)
UoB
Uo
Description
+ Input
- Input
Description
BI1, +
BI1, -
BI2, +
BI2, -
BI3, +
BI3, -
BI4, -
BI4, +
1MRS758272 B
REG615
Application Manual