ABB RELION 615 Series Applications Manual page 84

Generator and interconnection protection
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

Section 3
REG615 standard configurations
78
BLOCK_UV
BLOCK_UV
PHPTUV1_OPERATE
PHPTUV2_OPERATE
GUID-2D4EE8AA-C017-43A7-BE49-6569FF7BC09A V2 EN
Figure 86:
Undervoltage protection function
Two stages of each positive-sequence undervoltage PSPTUV and negative-sequence
overvoltage NSPTOV protection functions are also provided. A failure in the voltage
measuring circuit is detected by the fuse failure function. The fuse failure activation
is connected to block undervoltage protection functions and voltage based unbalance
protection functions to avoid faulty tripping. In addition, undervoltage protection is
also blocked when a generator circuit breaker is in open position.
SEQSPVC1_FUSEF_U
SEQSPVC1_FUSEF_U
NSPTOV1_OPERATE
NSPTOV2_OPERATE
GUID-6B465C7E-C870-4C22-97DF-01F7189CF8B5 V2 EN
Figure 87:
Negative sequence overvoltage protection function
PHPTUV1
BLOCK
OPERATE
START
PHPTUV2
BLOCK
OPERATE
START
OR
B1
O
B2
NSPTOV1
BLOCK
OPERATE
START
NSPTOV2
BLOCK
OPERATE
START
OR
B1
O
B2
1MRS758272 B
PHPTUV1_OPERATE
PHPTUV1_START
PHPTUV2_OPERATE
PHPTUV2_START
PHPTUV_OPERATE
NSPTOV1_OPERATE
NSPTOV1_START
NSPTOV2_OPERATE
NSPTOV2_START
NSPTOV_OPERATE
REG615
Application Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion reg615

Table of Contents