Generator and interconnection protection
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MRS758272 B
REG615
Application Manual
Table 2:
Plug-in unit and case
Main
Slot ID
Content options
Plug-in
-
HMI
unit
X100
Auxiliary power/BO
module
X110
BIO module
X120
AI/BI module
Case
X130
AI/BI module
AI/RTD/mA module
X000
Optional communication
module
1) The 0.2/1 A input is normally used in applications requiring sensitive earth-fault protection and featuring
core-balance current transformers.
Rated values of the current and voltage inputs are basic setting parameters of the
protection relay. The binary input thresholds are selectable within the range 16...176
V DC by adjusting the binary input setting parameters.
The connection diagrams of different hardware modules are presented in this manual.
REG615 overview
Small (5 lines, 20 characters)
Large (10 lines, 20 characters) with SLD
Small Chinese (3 lines, 8 or more characters)
Large Chinese (7 lines, 8 or more characters) with
SLD
48...250V DC/100...240 V AC; or 24...60 V DC
2 normally-open PO contacts
1 change-over SO contact
1 normally open SO contact
2 double-pole PO contacts with TCS
1 dedicated internal fault output contact
8 binary inputs
4 SO contacts
8 binary inputs
3 HSO contacts
Only with configurations A and C:
3 phase current inputs (1/5 A)
1 residual current input (1/5 A or 0.2/1 A)
4 binary inputs
Only with configuration D:
6 phase current inputs (1/5 A)
1 residual current input (1/5 A or 0.2/1 A)
3 phase voltage inputs (60...210 V)
1 residual voltage input (60...210 V)
4 binary inputs
Additionally with configurations A and D:
1 reference voltage input for SECRSYN1 (60...210
V)
Additionally with configuration C:
1 residual voltage input for H3EFPSEF1 (60...210 V)
3 phase voltage inputs (60...210 V)
1 residual voltage input (60...210 V)
1 generic mA inputs
2 RTD sensor inputs
Additionally with configurations A and D:
1 reference voltage input for SECRSYN1 (60...210
V)
Additionally with configuration C:
1 residual voltage input for H3EFPSEF1 (60...210 V)
See the technical manual for details about different
types of communication modules.