Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
Table of contents Table of contents Section 1 Introduction...............7 This manual..................7 Intended audience................7 Product documentation...............7 Product documentation set............7 Document revision history.............8 Related documentation..............8 Symbols and conventions..............9 Symbols..................9 Document conventions..............9 Functions, codes and symbols............10 Section 2 Modbus data mappings..........13 Overview...................13 Supported functions................13 Point list for REU615 Ver.4.0 UE01-02..........15 Indications...................15 CommonData1...............15...
Page 9
Table of contents LD0.MAPGAPC2 Multipurpose analog protection function (2)................35 LD0.MAPGAPC3 Multipurpose analog protection function (3)................36 LD0.MAPGAPC4 Multipurpose analog protection function (4)................36 LD0.MAPGAPC5 Multipurpose analog protection function (5)................36 LD0.MAPGAPC6 Multipurpose analog protection function (6)................36 LD0.XGGIO130 Physical I/O states (BIO card X130) ...37 CTRL.DCXSWI1 Controllable discon.
Page 10
Table of contents LD0.SECRSYN1 Synchrocheck..........50 Indication bits mirrored in registers........50 LD0.PEMSTA1 Power measurement demand values (1) ..................50 LD0.VMSTA1 Voltage demand values (1) ......51 LD0.RESVMSTA1 Residual voltage demand value (1) ..52 LD0.CMSTA1 Phase current demand values (1) ....52 CTRL.CBCSWI1 Circuit breaker operation counter (1) ..53 LD0.ARCSARCx1 Fault arc counters ........53 LD0.XRGGIO130 RTD input values........54 LD0.PEMMTR1 Three-phase energy measurements....54...
Page 11
Table of contents CTRL.DCCSWI1 Disconnector (1) control......69 CTRL.DCCSWI2 Disconnector (2) control......70 CTRL.ESCSWI1 Earth switch (1) control.......70 Section 3 Glossary.................71 REU615 Point List Manual...
Section 1 1MRS757057 B Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a...
Document revision/date Product version History A/2010-06-11 First release B/2012-05-11 Content updated to correspond to the product version Download the latest documents from the ABB Web site http://www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID Modbus Communication Protocol Manual 1MRS756468...
Section 1 1MRS757057 B Introduction Symbols and conventions 1.4.1 Symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
Section 2 1MRS757057 B Modbus data mappings Section 2 Modbus data mappings Overview This document describes the Modbus data points and structures available in REU615 Ver.4.0. The point lists describe a superset of all data available through the standard configurations A and B including the optional functionalities. The names of the standard configurations are UE01 and UE02 respectively.
Section 2 1MRS757057 B Modbus data mappings IEC 61850 UE01 UE02 CSMSQI1 ● VMMXU1 ● ● RESVMMXU1 ● VSMSQI1 ● ● PEMMXU1 ● XRGGIO130 FMMXU1 ● ● = available in the device variant, o = optionally available in the device variant Point list for REU615 Ver.4.0 UE01-02 2.3.1 Indications...
Section 2 1MRS757057 B Modbus data mappings 2.3.1.2 LD0.LEDPTRC1 Global conditioning Table 5: LD0.LEDPTRC1 Global conditioning BitA RegA IEC 61850 name SA name Description Values LD0.LEDPTRC1 2736 171.00 .Str.general Global start 1=Start 2737 171.01 .mcd 2738 171.02 .Op.general Global operate 1=Operate 2739 171.03...
Section 2 1MRS757057 B Modbus data mappings 2.3.1.13 CTRL.DCSXSWI3 Disconnector 3 mom position Table 16: CTRL.DCSXSWI3 Disconnector 3 mom position BitA RegA IEC 61850 name SA name Description Values CTRL.DCSXSWI3 POSITION 2798 174.14 .Pos.stVal.Close Close bit 1=Close 2799 174.15 .Pos.stVal.Open Open bit 1=Open 2800...
Section 2 1MRS757057 B Modbus data mappings 2.3.1.17 CTRL.CBCSWI1 Circuit breaker 1 mom+mcd position Table 20: CTRL.CBCSWI1 Circuit breaker 1 mom+mcd position BitA RegA IEC 61850 name SA name Description Values CTRL.CBCSWI1 POSITION 2816 176.00 .Pos.stVal.Close Close bit 1=Close 2817 176.01 .mcd 2818...
Section 2 1MRS757057 B Modbus data mappings 2.3.1.20 LD0.LEDPTRC1 Global conditioning - phase information Table 23: LD0.LEDPTRC1 Global conditioning - phase information BitA RegA IEC 61850 name SA name Description Values LD0.LEDPTRC1 2864 179.00 .Str.phsA Start phsA 1=Start 2865 179.01 .mcd 2866 179.02...
Section 2 1MRS757057 B Modbus data mappings 2.3.1.58 LD0.MAPGAPC3 Multipurpose analog protection function (3) Table 61: LD0.MAPGAPC3 Multipurpose analog protection function (3) BitA RegA IEC 61850 name SA name Description Values LD0.MAPGAPC3 3150 196.14 .Op.general OPERATE Stage operate 1 = Operate 3151 196.15 .mcd...
Section 2 1MRS757057 B Modbus data mappings 2.3.2.1 User definable registers [Alt.1], visible on 3x and 4x Table 77: User definable registers [Alt.1], visible on 3x and 4x RegA Scale IEC 61580 name SA name Description Values Obs PLC < not mappable- not visible > addr.
Section 2 1MRS757057 B Modbus data mappings 2.3.2.5 SSR3 System status register 3 - data available 1 (client-dependent) Table 81: SSR3 System status register 3 - data available 1 (client-dependent) RegA Scale IEC 61580 name SA name Description Values 130.00 Unread event records available 1=Available 130.01...
Section 2 1MRS757057 B Modbus data mappings 2.3.2.7 SSR5 System status register 5 - device alive register Table 83: SSR5 System status register 5 - device alive register RegA Scale IEC 61580 name SA name Description Values Device alive counter 0..65535 2.3.2.8 SSR6 System status register 6 - control command status (client-...
Section 2 1MRS757057 B Modbus data mappings 2.3.2.16 LD0.TPOSSLTC1 Tap changer position Table 92: LD0.TPOSSLTC1 Tap changer position RegA Scale IEC 61580 name SA name Description Values LD0.TPOSSLTC1 .TapPos.mag TAP_POS Tap changer position -64..63 2.3.2.17 LD0.FMMXU1 Frequency measurement Table 93: LD0.FMMXU1 Frequency measurement RegA Scale...
Section 2 1MRS757057 B Modbus data mappings 2.3.2.22 LD0.RESVMSTA1 Residual voltage demand value (1) Table 98: LD0.RESVMSTA1 Residual voltage demand value (1) RegA Scale IEC 61580 name SA name Description Values LD0.RESVMSTA1 Demand value 0.00..4.0 1977 1000 .AvVolts.mag U_DMD_RES - residual amplitude [xUn] Update time stamp See doc.
Section 2 1MRS757057 B Modbus data mappings RegA Scale IEC 61580 name SA name Description Values Update time stamp See doc. 2010 - Year - month 2011 - Day - hour 2012 - Minute - second 2013 - Milliseconds 2014 - Time quality 0.00..40.0 2015...
Section 2 1MRS757057 B Modbus data mappings 2.3.2.28 System diagnostic values Table 104: System diagnostic values RegA Scale IEC 61580 name SA name Description Values LD0.LPHD1 2050 .PhyHealth1.stVal Warning Last warning code see doc. 2051 .PhyHealth2.stVal Internal fault Last internal fault code see doc.
Section 2 1MRS757057 B Modbus data mappings 2.3.2.31 Control structure 2 Table 107: Control structure 2 RegA Scale IEC 61580 name SA name Description Values 8006 Execute register 8007 Password reg 1 acc to setting 8008 Password reg 2 acc to setting 8009 Control register <...
Section 2 1MRS757057 B Modbus data mappings 2.3.2.35 Control structure 6 Table 111: Control structure 6 RegA Scale IEC 61580 name SA name Description Values 8026 Execute register 8027 Password reg 1 acc to setting 8028 Password reg 2 acc to setting 8029 Control register <...
Section 2 1MRS757057 B Modbus data mappings 2.3.2.39 IED Real-time clock (in local time mode) - read and write (synchronize) Table 115: IED Real-time clock (in local time mode) - read and write (synchronize) RegA Scale IEC 61580 name SA name Description Values 0..2 (see...
Section 2 1MRS757057 B Modbus data mappings RegA Scale IEC 61580 name SA name Description Values 9228.0 - bit 0 1=Cold start 9228.1 - bit 1 1=Watchdog 9228.2 - bit 2 1=Warm start 2.3.2.42 Active parameter setting group - read and write Table 118: Active parameter setting group - read and write RegA...
Page 66
Section 2 1MRS757057 B Modbus data mappings RegA Scale IEC 61580 name SA name Description Values 9268 - Millisecond Millisecond 9269 Event identification see doc. 9270 Data object ID1 see doc. 9271 Data object ID2 see doc. 9272 Event data value 1 see doc.
Page 67
Section 2 1MRS757057 B Modbus data mappings RegA Scale IEC 61580 name SA name Description Values 9298 - Year, Month Year/Month 9299 - Day, Hour Day/Hour 9300 - Minute, Second Min/Sec 9301 - Millisecond Millisecond 9302 Event identification see doc. 9303 Data object ID1 see doc.
Page 68
Section 2 1MRS757057 B Modbus data mappings RegA Scale IEC 61580 name SA name Description Values 9329 - Record sequence num 1..9999 9330 - Unread records left 0..499 Timestamp of record 9331 - Year, Month Year/Month 9332 - Day, Hour Day/Hour 9333 - Minute, Second...
Section 2 1MRS757057 B Modbus data mappings RegA Scale IEC 61580 name SA name Description Values 9359 Data object ID2 see doc. 9360 Event data value 1 see doc. 9361 Event data value 2 see doc. 2.3.2.44 Fault record structure header Table 120: Fault record structure header RegA...
Section 2 1MRS757057 B Modbus data mappings 2.3.2.45 Fault record data Table 121: Fault record data RegA Scale IEC 61580 name SA name Description LD0.FLTMSTA1 9422 1000 .MaxAmpsA.mag Max phsA current 0..50.0 [xIn] 9423 1000 .MaxAmpsB.mag Max phsB current 0..50.0 [xIn] 9424 1000 .MaxAmpsC.mag...
Section 2 1MRS757057 B Modbus data mappings 2.3.3 Controls Table 122: Explanations of the controls table columns Column name Description IEC 61850 Original IED data object identification. Described in the IEC 61850 format as name Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the same as the application function block name.
Section 2 1MRS757057 B Modbus data mappings 2.3.3.12 LD0.SPCGGIO2 Multipurpose binary outputs (2) The binary outputs may be configured either as pulse- or persistent-type outputs. Pulse-type outputs are triggered with the write value "1". Persistent-type outputs can be written with both "1" and "0" values. The persistent type is the same as the toggled mode on LHMI and WHMI.
Section 2 1MRS757057 B Modbus data mappings 2.3.3.14 CTRL.DCCSWI2 Disconnector (2) control Table 136: CTRL.DCCSWI2 Disconnector (2) control IEC 61580 name SA name Description Values CTRL.DCCSWI2 2150 7.06 .Pos.Oper.ctlVal Select open 1=Select 2151 7.07 .Pos.Oper.ctlVal Select close 1=Select 2152 7.08 .Pos.Oper.ctlVal Cancel selection 1=Cancel...
Section 3 1MRS757057 B Glossary Section 3 Glossary 615 series Series of numerical IEDs for low-end protection and supervision applications of utility substations, and industrial switchgear and equipment Electromagnetic compatibility Human-machine interface International Electrotechnical Commission IEC 61850 International standard for substation communication and modeling Intelligent electronic device IET600...