ABB RELION 615 Series Applications Manual page 63

Generator and interconnection protection
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MRS758272 B
REG615
Application Manual
BLOCK_SECRSYN1
X110_BI1_TERMINAL_VT_MCB_OPEN
X110_BI2_BUSBARL_VT_MCB_OPEN
GUID-9704EA86-855D-42AC-8907-3CC6A0E118FC V2 EN
Figure 45:
Synchrocheck function
Two types of disconnector and earthing switch function blocks are available.
DCSXSWI1...3 and ESSXSWI1...2 are status only type and DCXSWI1...2 and
ESXSWI1 are controllable type. By default, the status only blocks are connected in a
standard configuration. The disconnector (CB truck) and line side earthing switch
status information is connected to DCSXSWI1 and ESSXSI1 respectively.
X110_BI4_CB_TRUCK_IN_TEST
X110_BI3_CB_TRUCK_IN_SERVICE
GUID-08EEEC94-1EAC-45CB-897F-C7E45AF80C32 V2 EN
Figure 46:
Disconnector control logic
X110_BI6_ES1_OPENED
X110_BI5_ES1_CLOSED
GUID-B1B96FFE-6504-4373-9143-0C9FD8B804B8 V2 EN
Figure 47:
Earth switch control logic
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The
input can be activated by the configuration logic, which is a combination of the
disconnector or breaker truck and the earth-switch position status and status of the trip
logics.
The OKPOS output from DCSXSWI defines whether the disconnector or breaker
truck is either open (in test position) or close (in service position). This output,
together with the open earth switch and non-active trip signals, activates the close-
enable signal to the circuit breaker control function block. The open operation for
circuit breaker is always enabled.
The SYNC_ITL_BYP input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position.
REG615 standard configurations
SECRSYN1(SYNC(1
BLOCK
SYNC_INPRO
CL_COMMAND
SYNC_OK
BYPASS
CL_FAIL_AL
CMD_FAIL_AL
LLDB
LLLB
DLLB
DLDB
OR6
B1
O
B2
B3
B4
B5
B6
DCSXSWI1(I<->O
POSOPEN
OPENPOS
POSCLOSE
CLOSEPOS
OKPOS
ESSXSWI1(I<->O
POSOPEN
OPENPOS
POSCLOSE
CLOSEPOS
OKPOS
Section 3
SECRSYN1_SYNC_OK
BLOCK_SECRSYN1
DCSXSWI1_OKPOS
ESSXSWI1_OPENPOS
57