ABB RELION 615 Series Applications Manual page 79

Generator and interconnection protection
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MRS758272 B
REG615
Application Manual
INRPHAR1_BLK2H
INRPHAR1_BLK2H
PHIPTOC1_OPERATE
PHLPTOC1_OPERATE
PHHPTOC1_OPERATE
GUID-4368AB17-6EEE-49A6-B3A3-072AFB612451 V2 EN
Figure 74:
Overcurrent protection function
SEQSPVC1_FUSEF_U
GUID-5B9BA191-7DC4-40A5-96F3-FAC1662560FE V2 EN
Figure 75:
Voltage dependent overcurrent protection function
The output BLK2H of three-phase inrush detector INRPHAR1 either blocks the
function or multiplies the active settings for any of the available overcurrent or earth-
fault function blocks. In the configuration, INRPHAR1 blocks the high and
instantaneous stage of non-directional overcurrent protection.
BLOCK
GUID-894F068C-661D-486D-B125-4A96CD9D614E V2 EN
Figure 76:
Inrush detector function
Two negative-sequence overcurrent protection stages MNSPTOC1 and MNSPTOC2
are provided for phase unbalance protection. These functions are used to protect
against unbalance conditions due to unbalance load or unsymmetrical faults.
REG615 standard configurations
PHIPTOC1(3I>>>(
BLOCK
OPERATE
ENA_MULT
PHHPTOC1(3I>>(1
BLOCK
OPERATE
ENA_MULT
PHLPTOC1(3I>(1)
BLOCK
OPERATE
ENA_MULT
OR6
B1
B2
B3
B4
B5
B6
PHPVOC1
BLOCK
OPERATE
ENA_MULT
START
ENA_LOW_LIM
INRPHAR1
BLK2H
Section 3
PHIPTOC1_OPERATE
START
PHIPTOC1_START
PHHPTOC1_OPERATE
START
PHHPTOC1_START
PHLPTOC1_OPERATE
START
PHLPTOC1_START
O
PHxPTOC_OPERATE
PHPVOC1_OPERATE
PHPVOC1_START
INRPHAR1_BLK2H
73