1MRS758272 B
3.4.2
3×
U
L1, L2, L3
Uo
Io
G
3I
EXC.
AVR
Io
∆Io
2×RTD
1×mA
Uo
GUID-1536B574-54F9-4C47-BD65-175410DFEE46 V2 EN
Figure 73:
Functionality overview for standard configuration C
REG615
Application Manual
further adapted to different primary circuit layouts and the related functionality needs
by modifying the internal functionality using PCM600.
Functions
REG615
GENERATOR PROTECTION RELAY
PROTECTION
2×
3×
Master Trip
Master Trip
Lockout relay
Lockout relay
94/86
94/86
Master Trip
Lockout relay
94/86
2×
3Ith>T/G/C
I2>M
49T/G/C
46M
3×
ARC
3I>/Io>BF
50L/50NL
51BF/51NBF
3I>
3I>>
3I(U)>
51P-1
51P-2
51V
3×
Z<G
P>/Q>
21G
32R/32O
X<
OOS
40
78
Io
dUo>/Uo3H
Io>>
27/59THD
51N-2
2×
Io>→
Io>>→
67N-1
67N-2
2×
2×
U/f>
3U<
U2>
24
27
47O-
2×
6×
f>/f<,
3U>
df/dt
59
81
18×
MAP
MAP
REG615 standard configurations
LOCAL HMI
A
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
I
ESC
O
3I>>>
50P/51P
CONDITION MONITORING
AND SUPERVISION
3I
3I2f>
FUSEF
CBCM
68
60
CBCM
U
L1, L2, L3
2×
TCS
2×
TCM
P<
32U
CONTROL AND INDICATION
Object
2×
CB
Uo>
DC
59G
ES
Check availability of binary inputs/outputs
1)
from technical documentation
Control and indication function for
2)
primary object
Status indication function for
3)
primary object
2×
U1<
47U+
REMARKS
Optional
function
STANDARD
CONFIGURATION
ALSO AVAILABLE
- Disturbance and fault recorders
- Event log and recorded data
Configuration
A
- High-Speed Output module (optional)
System
HMI
Time
Authorization
- Local/Remote push button on LHMI
I
ESC
Clear
- Self-supervision
O
- Time synchronization: IEEE 1588 v2,
R
L
SNTP, IRIG-B
- User management
- Web HMI
Clear
R
L
COMMUNICATION
Protocols:
IEC 61850-8-1/-9-2LE
Modbus
®
IEC 60870-5-103
DNP3
OPTS
Interfaces:
OPTM
Ethernet: TX (RJ45), FX (LC)
Serial:
Serial glass fiber (ST),
RS-485, RS-232
Redundant protocols:
HSR
PRP
RSTP
MEASUREMENT
1)
- I, U, Io, Uo, P, Q, E, pf, f
Ctrl
Ind
2)
3)
- Limit value supervision
- Load profile record
1
-
- RTD/mA measurement (optional)
2
3
- Symmetrical components
- Frequency adaptivity
1
2
Analog interface types
Current transformer
Voltage transformer
1)
Conventional transformer inputs
PQM3I
PQM3U
PQM3I
PQM3V
PQUUB
PQVUB
No. of
Calculated
3×
OR
instances
value
Io/Uo
Section 3
C
AND
OR
1)
4
5
PQMU
PQMV
Alternative
function to be
defined when
ordering
67