Functional Diagrams For Control And Interlocking - ABB RELION 615 Series Applications Manual

Generator and interconnection protection
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

Section 3
REG615 standard configurations
3.5.3.4
120
TCSSCBR1_BLOCKING
TCSSCBR2_BLOCKING
TCSSCBR1_ALARM
TCSSCBR2_ALARM
GUID-A12C8E2E-059C-4F5B-84FB-FC015D943EB8 V2 EN
Figure 162:
Trip circuit supervision function
TRPPTRC1_TRIP
TRPPTRC2_TRIP
X110_BI8_CB_OPENED
TRPPTRC6_TRIP_FIELD_EXCITATION
X130_BI4_FIELD_EXCITATION_OPEN
GUID-8E5934D3-3BAB-45FD-AEC6-63A9CE01815B V2 EN
Figure 163:
Logic for blocking of trip circuit supervision
Runtime counter for machines and devices MDSOPT provides history data since the
last commissioning. The counter counts the total number of generator running hours
and is incremented when the energizing circuit breaker is closed.
X110_BI7_CB_CLOSED
GUID-1E56C486-0477-445F-8E31-F5237B34E27D V2 EN
Figure 164:
Generator runtime counter

Functional diagrams for control and interlocking

The main purpose of the synchronism and energizing check SECRSYN is to provide
control over the closing of the circuit breakers in power networks to prevent the
closing if conditions for synchronism are not detected. The energizing function allows
closing, for example, when one side of the breaker is dead.
SECRSYN measures the bus and line voltages and compares them to set conditions.
When all the measured quantities are within set limits, the output SYNC_OK is
TCSSCBR1
BLOCK
ALARM
TCSSCBR2
BLOCK
ALARM
OR
B1
O
B2
OR6
B1
O
B2
B3
B4
B5
B6
OR6
B1
O
B2
B3
B4
B5
B6
MDSOPT1
BLOCK
ALARM
POS_ACTIVE
WARNING
RESET
1MRS758272 B
TCSSCBR1_ALARM
TCSSCBR2_ALARM
TCSSCBR_ALARM
TCSSCBR1_BLOCKING
TCSSCBR2_BLOCKING
MDSOPT1_ALARM
REG615