ABB RELION 615 Series Applications Manual page 64

Generator and interconnection protection
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

Section 3
REG615 standard configurations
58
SYNC_ITL_BYP overrides, for example, active interlocking conditions when the
circuit breaker truck is closed in service position.
Connect the additional signals required for the application for closing
and opening of circuit breaker.
X110_BI8_CB_OPENED
X110_BI7_CB_CLOSED
TRUE
CBXCBR1_ENA_CLOSE
FALSE
CBXCBR1_BLK_CLOSE
CBXCBR1_AU_OPEN
CBXCBR1_AU_CLOSE
SECRSYN1_SYNC_OK
GUID-BB1ED650-9B7D-48FB-A353-9AA6702904E2 V2 EN
Figure 48:
Circuit breaker 1 control logic
CBXCBR1_EXE_CL
GUID-F56A6CCD-63A7-46DE-A278-577732873C08 V2 EN
Figure 49:
Signal for closing coil of circuit breaker 1
TRPPTRC1_TRIP
CBXCBR1_EXE_OP
GUID-AC90C2DE-F775-4710-B79C-0073FFD6E25A V2 EN
Figure 50:
Signal for opening coil of circuit breaker 1
ESSXSWI1_OPENPOS
IN
TRPPTRC1_TRIP
IN
TRPPTRC2_TRIP
GUID-12D10670-281F-4E83-9AF0-D0F00CE8A38F V2 EN
Figure 51:
Circuit breaker 1 close enable logic
Connect the higher-priority conditions before enabling the closing of
circuit breaker. These conditions cannot be bypassed using bypass
feature of the function.
CBXCBR1(I<->O C
POSOPEN
POSCLOSE
ENA_OPEN
ENA_CLOSE
BLK_OPEN
BLK_CLOSE
AU_OPEN
AU_CLOSE
TRIP
SYNC_OK
SYNC_ITL_BYP
OR
B1
B2
OR6
B1
B2
B3
B4
B5
B6
B1
DCSXSWI1_OKPOS
B2
B3
B4
B5
NOT
B6
OUT
NOT
OUT
1MRS758272 B
SELECTED
EXE_OP
CBXCBR1_EXE_OP
EXE_CL
CBXCBR1_EXE_CL
OP_REQ
CL_REQ
OPENPOS
CLOSEPOS
OKPOS
OPEN_ENAD
CLOSE_ENAD
O
CB_CLOSE_COMMAND
O
CB_OPEN_COMMAND
AND6
O
CBXCBR1_ENA_CLOSE
Application Manual
REG615