Functional Diagram For Measurement Functions - ABB RELION 615 Series Applications Manual

Generator and interconnection protection
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

Section 3
REG615 standard configurations
3.5.3.5
122
Connect the additional signals required for the application for opening
of circuit breaker.
X110_BI8_CB_OPENED
X110_BI7_CB_CLOSED
TRUE
FALSE
FALSE
CBXCBR1_AU_OPEN
SECRSYN1_SYNC_OK
GUID-84F06254-AEDB-4767-84CC-451E75B412B8 V2 EN
Figure 168:
Circuit breaker 1 control logic
TRPPTRC1_TRIP
CBXCBR1_EXE_OP
GUID-7AF037D4-8275-4799-8C58-344F333CBC53 V2 EN
Figure 169:
Signal for opening coil of circuit breaker 1
The configuration includes the logic for generating circuit breaker external opening
command with the relay in local or remote mode.
Connect additional signals for opening of circuit breaker in local or
remote mode, if applicable for the configuration.
CONTROL_LOCAL
FALSE
CONTROL_REMOTE
FALSE
GUID-068A0FE9-D673-4746-A033-CD61F70FA26D V2 EN
Figure 170:
External opening command for circuit breaker 1

Functional diagram for measurement functions

The neutral side and terminal side phase current inputs to the relay are measured by the
three-phase current measurement CMMXU1 and CMMXU2. The three-phase current
input is connected to the X120 card in the back panel. The neutral side sequence
current measurement is measured by CSMSQI1 and the residual current measurement
RESCMMXU1 measures the residual current.
CBXCBR1
POSOPEN
POSCLOSE
ENA_OPEN
ENA_CLOSE
BLK_OPEN
BLK_CLOSE
AU_OPEN
AU_CLOSE
TRIP
SYNC_OK
CLOSE_ENAD
SYNC_ITL_BYP
OR6
B1
B2
B3
B4
B5
B6
AND
B1
O
B2
B1
B2
AND
B1
O
B2
SELECTED
EXE_OP
CBXCBR1_EXE_OP
EXE_CL
OP_REQ
CL_REQ
OPENPOS
CLOSEPOS
OKPOS
OPEN_ENAD
O
CB_OPEN_COMMAND
OR
O
CBXCBR1_AU_OPEN
Application Manual
1MRS758272 B