1MRS758272 B
3.5.2.2
REG615
Application Manual
LED
Description
7
Thermal overload of NPS protection operated
8
Disturbance recorder triggered
9
Supervision alarms
10
Arc fault detected
11
Circuit breaker failure protection operated
Default disturbance recorder settings
Table 24:
Default disturbance recorder analog channels
Channel
Description
1
IL1
2
IL2
3
IL3
4
IL1B
5
IL2B
6
IL3B
7
Io
8
Uo
9
U1
10
U2
11
U3
12
U1B
Table 25:
Default disturbance recorder binary channels
Channel
ID text
1
PHLPTOC1 - start
2
PHHPTOC1 - start
3
PHIPTOC2 - start
4
PHPVOC1 - start
8
DEFLPDEF1 - start
9
DEFLPDEF2 - start
10
DEFHPDEF1 - start
11
EFHPTOC1 - start
12
MNSPTOC1 - start
13
MNSPTOC2 - start
18
DOPPDPR1 - start
19
DOPPDPR2 - start
21
DUPPDPR1 - start
22
DUPPDPR2 - start
Table continues on next page
REG615 standard configurations
Section 3
Level trigger mode
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
103