Section 3 Red615 Standard Configurations; Standard Configurations - ABB RELION 615 Series Applications Manual

Line differential protection and control
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MAC807603-MB A
Section 3
3.1
RED615 ANSI
Application Manual
RED615 standard configurations

Standard configurations

RED615 is available with two alternative standard configurations. The standard signal
configuration can be altered by means of the signal matrix or the graphical application
functionality of the Protection and Control IED Manager PCM600. Further, the
application configuration functionality of PCM600 supports the creation of multi-layer
logic functions utilizing various logical elements including timers and flip-flops. By
combining protection functions with logic function blocks the relay configuration can be
adapted to user specific application requirements.
The relay is delivered from the factory with default connections described in the
functional diagrams for binary inputs, binary outputs, function-to-function connections
and alarm LEDs. Some of the supported functions in RED615 must be added with the
Application Configuration tool to be available in the Signal Matrix tool and in the relay.
The positive measuring direction of directional protection functions is towards the
outgoing feeder.
Table 7:
Standard configurations
Description
Line differential protection with directional overcurrent and ground-fault protection, voltage
and frequency based protection and measurements, synchro-check and circuit-breaker
condition monitoring (RTD option, optional power quality and fault locator)
Line differential protection with directional overcurrent and ground-fault protection, voltage
and frequency based protection and measurements, and circuit-breaker condition
monitoring (sensor inputs, optional power quality, fault locator and synchro-check with IEC
61850-9-2 LE)
Table 8:
Supported functions
Function
Protection
Three-phase non-directional overcurrent
protection, instantaneous stage
Three-phase directional overcurrent
protection, low stage
Three-phase directional overcurrent
protection, high stage
Table continues on next page
RED615 standard configurations
IEC 61850
ANSI
PHIPTOC
50P-3
DPHLPDOC
67/51P
DPHHPDOC
67/50P
Section 3
Std. conf.
D
E
D
E
1
1
2
2
1
1
27