Section 3 Rev615 Standard Configurations; Standard Configurations - ABB RELION 615 Series Applications Manual

Capacitor bank protection and control
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MRS758955 A
Section 3
3.1
REV615
Application Manual
REV615 standard configurations

Standard configurations

REV615 is available with one standard configuration. The standard signal
configuration can be altered by means of the signal matrix or the graphical application
functionality of the Protection and Control IED Manager PCM600. Further, the
application configuration functionality of PCM600 supports the creation of multi-
layer logic functions using various logical elements, including timers and flip-flops.
By combining protection functions with logic function blocks, the relay configuration
can be adapted to user-specific application requirements.
The relay is delivered from the factory with default connections described in the
functional diagrams for binary inputs, binary outputs, function-to-function
connections and alarm LEDs. Some of the supported functions in REV615 must be
added with the Application Configuration tool to be available in the Signal Matrix tool
and in the relay. The positive measuring direction of directional protection functions
is towards the outgoing feeder.
Table 9:
Standard configurations
Description
Capacitor bank overload and unbalance protection, non-directional overcurrent and
directional earth-fault protection, voltage and frequency based protection and
measurements, and circuit-breaker condition monitoring
Table 10:
Supported functions
Function
Protection
Three-phase non-directional overcurrent protection, low stage
Three-phase non-directional overcurrent protection, high stage
Three-phase non-directional overcurrent protection, instantaneous stage
Non-directional earth-fault protection, high stage
Directional earth-fault protection, low stage
Directional earth-fault protection, high stage
Transient/intermittent earth-fault protection
Negative-sequence overcurrent protection
Residual overvoltage protection
Three-phase undervoltage protection
Three-phase overvoltage protection
Table continues on next page
REV615 standard configurations
Section 3
Std. conf.
B
IEC 61850
B
PHLPTOC
1
PHHPTOC
2
PHIPTOC
1
EFHPTOC
1
DEFLPDEF
2
DEFHPDEF
1
INTRPTEF
1)
1
NSPTOC
2
ROVPTOV
1
2)
2
PHPTUV
2
PHPTOV
2
27