Standard configurable logic blocks

OR function block

Functionality
OR and OR6 are used to form general combinatory expressions with Boolean variables.
The O output is activated when at least one input has the value TRUE. The default value
of all inputs is FALSE, which makes it possible to use only the required number of inputs
and leave the rest disconnected.
OR has two inputs and OR6 has six inputs.
Function block
GUID-9D001113-8912-440D-B206-051DED17A23C V1 EN
Figure 42:
Function blocks
Settings
The function does not have any parameters available in LHMI or PCM600.

AND function block

Functionality
AND and AND6 are used to form general combinatory expressions with Boolean
variables.
The default value in all inputs is logical true, which makes it possible to use only the
required number of inputs and leave the rest disconnected.
Values (Range)
Unit
0=False
1=True
0=False
1=True
1...8
1MRS240050-IB C
Description
Status of output 7
Status of output 8
Present output position