Install and remove the device only when the power is off.
Switch off the power supply of the device before you install or remove the device. Installing
and removing devices with the power supply on can lead to damage to the devices and to
loss of data.
Installation options
You have the following options to install the gateway:
● Wall mounting
● Mounting on the following rail types (rack):
– DIN rail
– S7-1500 standard rail
– S7-300 standard rail
You can find suitable standard rails in the Siemens accessories program for automation
technology, for example:
35 mm standard mounting rail for 19" cabinets, article numbers 6ES5710-8MA11
● Mounting on pedestal
You can use the SCALANCE M pedestal "6GK5898-8MD00" for table mounting (does not
ship with the product).
Installation location
NOTICE
Installation location - Dependency of the temperature range
Note the dependency of the permitted temperature range of the installation location.
• Horizontal installation of the rack (DIN rail) means a vertical position of the modules.
• Vertical installation of the rack (DIN rail) means a horizontal position of the modules.
You will find the permitted temperature ranges in the section Technical specifications
(Page 99).
Minimum clearances
Mount the device so that its upper and lower ventilation slits are not covered, allowing
adequate ventilation as protection from overheating.
Keep to the following minimum clearances for the circulation of air when the rack is
installed horizontally:
• Above the device: At least 33 mm
• Below the device: At least 25 mm
SIMATIC CC712
Operating Instructions, 05/2019, C79000-G8976-C503-01
Installation, wiring, commissioning