Integrate the meter with the control system
Overview
An enhanced event is used to provide notification of process changes. An enhanced event
occurs (is ON) if the real-time value of a user-specified process variable moves above (HI)
or below (LO) a user-defined setpoint, or in range (IN) or out of range (OUT) with respect
to two user-defined setpoints. You can define up to five enhanced events.
Procedure
1.
2.
3.
4.
5.
Related information
10.5
Configure HART/Bell 202 communications
HART/Bell 202 communications parameters support HART communications with the
transmitter's primary mA terminals over a HART/Bell 202 network.
106
Select the event that you want to configure.
Specify Event Type.
Option
Description
HI
x > A
The event occurs when the value of the assigned process variable (x) is
greater than the setpoint (Setpoint A), endpoint not included.
LO
x < A
The event occurs when the value of the assigned process variable (x) is
less than the setpoint (Setpoint A), endpoint not included.
IN
A ≤ x ≤ B
The event occurs when the value of the assigned process variable (x) is in
range, that is, between Setpoint A and Setpoint B, endpoints included.
OUT
x ≤ A or x ≥ B
The event occurs when the value of the assigned process variable (x) is
out of range, that is, less than Setpoint A or greater than Setpoint B, end-
points included.
Assign a process variable to the event.
Set values for the required setpoints.
•
For HI and LO events, set Setpoint A.
•
For IN and OUT events, set Setpoint A and Setpoint B.
(Optional) Configure a discrete output to switch states in response to the event
status.
Configure Discrete Output Source
®
Micro Motion
Gas Specific Gravity Meters (SGM)