Analog Monitor [G] [Wg]; Setting Method - Mitsubishi Electric MR-J5 Series User Manual

Ac servo system
Hide thumbs Also See for MR-J5 Series:
Table of Contents

Advertisement

5.3

Analog monitor [G] [WG]

Voltage of the analog monitor output may be irregular at power-on.
The status of the servo amplifier, such as the servo motor speed, torque, and bus voltage can be outputted to two channels
with the voltage at the same time.

Setting method

In extension setting of MR Configurator2, the signals outputted by the analog monitor 1 and analog monitor 2 can be selected,
and the offset voltage of analog monitor can be set. The setting range of the offset voltage is -999 mV to 999 mV.
Servo
Symbol
parameter
PC09.0-1
MOD1
PC09.3
MOD1
PC10.0-1
MOD2
PC10.3
MOD2
PC11
MO1
PC12
MO2
Name
Outline
Analog monitor 1 output
Select the signal to be outputted to analog monitor 1. Refer to the following for
selection
setting values.
Page 240 Setting
Analog monitor output 1
Select the axis to be monitored with the analog monitor 1. This servo parameter can
output axis selection
be used with MR-J5W_-_G.
0: A-axis (initial value)
1: B-axis
2: C-axis
Analog monitor 2 output
Select the signal to be outputted to analog monitor 2. Refer to the following for
selection
setting values.
Page 240 Setting
Analog monitor output 2
Select the axis to be monitored with the analog monitor 2. This servo parameter can
output axis selection
be used with MR-J5W_-_G.
0: A-axis (initial value)
1: B-axis
2: C-axis
Analog monitor 1 offset
Set the offset voltage of MO1 (Analog monitor 1).
Initial value: 0 [mV]
Analog monitor 2 offset
Set the offset voltage of MO2 (Analog monitor 2).
Initial value: 0 [mV]
5 MONITOR
5.3 Analog monitor [G] [WG]
5
239