Mitsubishi Electric MR-J5 Series User Manual page 125

Ac servo system
Hide thumbs Also See for MR-J5 Series:
Table of Contents

Advertisement

Timing chart
■When instantaneous power failure time of control circuit power supply > [Pr. PF25 SEMI-F47
function - Instantaneous power failure detection time]
The alarm occurs when the instantaneous power failure time of the control circuit power supply exceeds [Pr. PF25 SEMI-F47
function - Instantaneous power failure detection time]. MTTR (During tough drive) turns on after the instantaneous power
failure is detected.
MBR (Electromagnetic brake interlock) turns off when the alarm occurs.
ON
Control circuit
OFF
power supply
Bus voltage
*1
Undervoltage level
ON
ALM
(Malfunction)
OFF
ON
WNG
(Warning)
OFF
ON
MTTR
(During tough drive)
OFF
ON
MBR
(Electromagnetic
OFF
brake interlock)
ON
Base circuit
OFF
*1 For the undervoltage level, refer to the following table.
Page 126 Operation contents
Instantaneous power failure time of control circuit power supply
[Pr. PF25]
4 APPLICABLE FUNCTION
4.1 Tough drive function
4
123