Operable Flow Range; Output; Output Signal - Endress+Hauser Proline Promass E 100 Manual

Coriolis flowmeter
Hide thumbs Also See for Proline Promass E 100:
Table of Contents

Advertisement

Proline Promass E 100

Operable flow range

Output signal

Endress+Hauser
Заказывайте на сайте: www.tinnova.ru/endress_hauser/ || Эл. почта: info@tinnova.ru
Maximum possible full scale value:
= 
· ρ
: x = 70 000 kg/h · 60.3 kg/m³ : 125 kg/m³ = 33 800 kg/h
max(G)
max(F)
G
Recommended measuring range
"Flow limit" section →  53
Over 1000 : 1.
Flow rates above the preset full scale value do not override the electronics unit, with the result that
the totalizer values are registered correctly.

Output

HART current output
Current output
4-20 mA HART (active)
Maximum output values
• DC 24 V (no flow)
• 22.5 mA
Load
0 to 700 Ω
Resolution
0.38 µA
Damping
Adjustable: 0.07 to 999 s
Assignable measured
• Mass flow
variables
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
Pulse/frequency/switch output
Function
Can be set to pulse, frequency or switch output
Version
Passive, open collector
Maximum input values
• DC 30 V
• 25 mA
Voltage drop
For 25 mA: ≤ DC 2 V
Pulse output
Pulse width
Adjustable: 0.05 to 2 000 ms
Maximum pulse rate
10 000 Impulse/s
Pulse value
Adjustable
Assignable measured
• Mass flow
variables
• Volume flow
• Corrected volume flow
Frequency output
Output frequency
Adjustable: 0 to 10 000 Hz
Damping
Adjustable: 0 to 999 s
Pulse/pause ratio
1:1
The range of options increases if the measuring device has one or more
application packages.
9