Current output 4 to 20 mA
4 to 20 mA
Failure mode
Choose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value
Pulse/frequency/switch output
Pulse output
Failure mode
Choose from:
• Actual value
• No pulses
Frequency output
Failure mode
Choose from:
• Actual value
• 0 Hz
• Defined value: 0 to 12 500 Hz
Switch output
Failure mode
Choose from:
• Current status
• Open
• Closed
PROFIBUS DP
Status and alarm
Diagnostics in accordance with PROFIBUS PA Profile 3.02
messages
Modbus RS485
Failure mode
Choose from:
• NaN value instead of current value
• Last valid value
EtherNet/IP
Device diagnostics
Device condition can be read out in Input Assembly
PROFINET
Device diagnostics
According to "Application Layer protocol for decentralized periphery", Version 2.3