PROFIBUS DP
The IEC 61158 standard specifies two types of cable (A and B) for the bus line which can be used for
every transmission rate. Cable type A is recommended.
Cable type
A
Characteristic impedance
135 to 165 Ω at a measuring frequency of 3 to 20 MHz
Cable capacitance
< 30 pF/m
Wire cross-section
> 0.34 mm
Cable type
Twisted pairs
Loop resistance
≤110 Ω/km
Signal damping
Max. 9 dB over the entire length of the cable cross-section
Shield
Copper braided shielding or braided shielding with foil shield. When grounding
the cable shield, observe the grounding concept of the plant.
Modbus RS485
The EIA/TIA-485 standard specifies two types of cable (A and B) for the bus line which can be used
for every transmission rate. Cable type A is recommended.
Cable type
A
Characteristic impedance
135 to 165 Ω at a measuring frequency of 3 to 20 MHz
Cable capacitance
< 30 pF/m
Wire cross-section
> 0.34 mm
Cable type
Twisted pairs
Loop resistance
≤110 Ω/km
Signal damping
Max. 9 dB over the entire length of the cable cross-section
Shield
Copper braided shielding or braided shielding with foil shield. When grounding
the cable shield, observe the grounding concept of the plant.
EtherNet/IP
The standard ANSI/TIA/EIA-568-B.2 Annex specifies CAT 5 as the minimum category for a cable
used for EtherNet/IP. CAT 5e and CAT 6 are recommended.
For more information on planning and installing EtherNet/IP networks, please refer to the
"Media Planning and Installation Manual. EtherNet/IP" of ODVA Organization
PROFINET
Standard IEC 61156-6 specifies CAT 5 as the minimum category for a cable used for PROFINET. CAT
5e and CAT 6 are recommended.
For more information on planning and installing PROFINET networks, see: "PROFINET Cabling
and Interconnection Technology", Guideline for PROFINET
Connecting cable between Safety Barrier Promass 100 and measuring device
Cable type
Shielded twisted-pair cable with 2x2 wires. When grounding the cable shield,
observe the grounding concept of the plant.
Maximum cable resistance 2.5 Ω, one side
Comply with the maximum cable resistance specifications to ensure the operational reliability
of the measuring device.