Dynamic variables
Device variables
PROFIBUS DP
Manufacturer ID
Ident number
Profile version
Device description files (GSD,
DTM, DD)
Read out the dynamic variables: HART command 3
The measured variables can be freely assigned to the dynamic variables.
Measured variables for PV (primary dynamic variable)
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
Measured variables for SV, TV, QV (secondary, tertiary and quaternary
dynamic variable)
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Totalizer 1
• Totalizer 2
• Totalizer 3
The range of options increases if the measuring device has one or more
application packages.
Heartbeat Technology application package
Additional measured variables are available with the Heartbeat Technology
application package:
Oscillation amplitude 0
Read out the device variables: HART command 9
The device variables are permanently assigned.
A maximum of 8 device variables can be transmitted:
• 0 = mass flow
• 1 = volume flow
• 2 = corrected volume flow
• 3 = density
• 4 = reference density
• 5 = temperature
• 6 = totalizer 1
• 7 = totalizer 2
• 8 = totalizer 3
• 13 = target mass flow
• 14 = carrier mass flow
• 15 = concentration
0x11
0x1561
3.02
Information and files under:
www.endress.com
On the product page for the device: Documents/Software → Device drivers
www.profibus.org
Proline Promass E 100
Endress+Hauser