238 •
I/O Modules
Process Data Architecture for EtherNet/IP
2 Channel Analog Input Modules
750-452, -454, -456, -461, -462, -465, -466, -467, -469, -472, -474, -475, -476,
-477, -478, -479, -480, -481, -483, -485, -492, (and all variations),
753-452, -454, -456, -461, -465, -466, -467, -469, -472, -474, -475, -476, -477,
-478, -479, -483, -492, (and all variations)
The input modules represent 2x2 bytes and seize 2 Instances in Class (0x67).
4 Channel Analog Input Modules
750-453, -455, -457, -459, -460, -468, (and all variations),
753-453, -455, -457, -459
The input modules represent 4x2 bytes and seize 4 Instances in Class (0x67).
Byte Destination
Offset
High Byte
0
D1
1
D3
Byte Destination
Offset
High Byte
0
D1
1
D3
2
D5
3
D7
Input Process Image
Low Byte
D0
Measured Value Channel 1
D2
Measured Value Channel 2
Input Process Image
Low Byte
D0
Measured Value Channel 1
D2
Measured Value Channel 2
D4
Measured Value Channel 3
D6
Measured Value Channel 4