10. Accept changes in the node configuration and close the dialog box by
11. You can change now the access authorization, if for individual modules, the
12. When you have completed the assignments, you can start programming with
More information
For a detailed description on how to use the software WAGO-I/O-PRO CAA
and the I/O-Configurator, please refer to the Online-Help of WAGO-I/O-PRO
CAA.
Note
Alternatively, the "EA-config.xml" file can be created with each editor and
then be transported via FTP in the Controller directory "/etc".
The configuration with the "EA-config.xml" file, which is already stored in
the controller, is described in the following chapter.
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
pressing the 'OK' button. The addresses in the PLC-configuration are
recalculated and the tree structure is refreshed afterwards.
write access should be via the fieldbus (MODBUS TCP/IP or Ethernet/IP).
For each module added, the write access first is fixed from the PLC.
You can change it by determining in the right-hand dialogue
window/register "Module parameters for each individual module, from
where the write access on the I/O Module data should take place.
For this in the "Value" column. your options include:
- PLC (The PFC controls its I/O locally)
- fieldbus 1 (A MODBUS TCP Fieldbus Master controls the I/O module)
- fieldbus 2 (An Ethernet IP Fieldbus Master controls the I/O module)
the IEC 61131-3 program tool. The configuration file "EA-config.xml" is
generated as soon as you compile the project.
Fieldbus Controller
Fieldbus Controller 750-872/020-000
• 79