And the specialty modules represent 1x6 bytes output data and seize 1
Instance in Class (0x68).
750-404/000-005
The above Counter Modules have a total of 5 bytes of user data in both the
Input and Output Process Image (4 bytes of counter data and 1 byte of
control/status). The two counter values are supplied as 16 bits. The following
tables illustrate the Input and Output Process Image, which has a total of 3
words mapped into each image. Word alignment is applied.
The specialty modules represent 1x6 bytes input data and seize 1 Instance in
Class (0x67).
And the specialty modules represent 1x6 bytes output data and seize 1
Instance in Class (0x68).
750-638, 753-638
The above Counter Modules have a total of 6 bytes of user data in both the
Input and Output Process Image (4 bytes of counter data and 2 bytes of
control/status). The two counter values are supplied as 16 bits. The following
tables illustrate the Input and Output Process Image, which has a total of 4
words mapped into each image. Word alignment is applied.
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
Byte Destination
Offset
High Byte
0
-
1
D1
2
D3
Byte Destination
Offset
High Byte
0
-
1
D1
2
D3
Byte Destination
Offset
High Byte
0
-
1
D1
2
D3
Process Data Architecture for EtherNet/IP
Output Process Image
Low Byte
C
D0
Counter Setting Value
D2
Input Process Image
Low Byte
S
D0
Counter Value of Counter 1
D2
Counter Value of Counter 2
Output Process Image
Low Byte
C
D0
Counter Setting Value of Counter 1
D2
Counter Setting Value of Counter 2
I/O Modules
Remark
Control byte
Remark
Status byte
Remark
Control byte
• 241