WAGO 750-872/020-000 Manual page 80

Modular i/o-system, programmable fieldbus controller for telecontrol applications
Table of Contents

Advertisement

72 •
Fieldbus Controller
Fieldbus Controller 750-872/020-000
3. Cursor to the text line: "node1:ht=1:ha=0030DE000100:ip=10.1.254.100"
4. If you want to give your fieldbus node a different name, replace the name
5. To assign the controller an IP address, replace the IP address specified in the
6. Because the second example is not necessary in this exercise, insert a "#" in
Note
To address more than one fieldbus nodes, add a line of setup information for
each additional PFC in the file bootptab.txt . Use steps 2 through 4 as a
guideline for configuring each additional module.
7. Save the new settings in the text file "bootptab.txt". To do this, go to the
BootP Server
8. Now open the dialog window for the WAGO BootP server by going to the
9. After the editor closes, Click on the Start button in the opened BootP dialog
The examples mentioned above contain the following information:
Declaration
Meaning
node1,
Any name can be given for the node here.
node2
ht=1
Specify the hardware type of the network here.
The hardware type for ETHERNET is 1.
ha=0030DE000100
Specify the hardware address or the MAC-ID of the ETHERNET
ha=0030DE000200
fieldbus controller (hexadecimal).
ip= 10.1.254.100
Enter the IP address of the ETHERNET fieldbus controller (decimal)
ip= 10.1.254.200
here.
T3=0A.01.FE.01
Specify the gateway IP address here.
Write the address in hexadecimal form.
Sm=255.255.0.0
In addition enter the Subnet-mask of the subnet (decimal), where the
ETHERNET fieldbus controller belongs to.
No gateway is required for the local network described in this example.
Therefore, the first example: "Example of entry with no gateway" can be
used.
and replace the 12 character hardware address, which is entered after "ha=",
with your PFC's MAC-ID.
"node1" with your new name.
example, which is entered immediately after "ip=", with the IP address you
have selected. Make sure you separate the 3 digit numbers with a decimal
point.
front of the text line of the second example: "# hamburg:hat=1:ha=003 0DE
0002 00:ip=10.1.254.200:T3=0A.01.FE.01", so that this line will be ignored.
File menu, menu item Save, and then close the editor.
Start menu on your screen surface, menu item Program /
WAGO Software / WAGO BootP Server and click on WAGO BootP
Server.
window. This will activate the inquiry/response mechanism of the BootP
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP