WAGO 750-872/020-000 Manual page 237

Modular i/o-system, programmable fieldbus controller for telecontrol applications
Table of Contents

Advertisement

AS-interface Master Module
750-655
The length of the process image of the AS-interface master module can be set
to fixed sizes of 12, 20, 24, 32, 40 or 48 bytes.
It consists of a control or status byte, a mailbox with a size of 0, 6, 10, 12 or
18 bytes and the AS-interface process data, which can range from 0 to 32
bytes.
The AS-interface master module has a total of 6 to maximally 24 words data
in both the Input and Output Process Image. Word alignment is applied.
The first Input and output word, which is assigned to an AS-interface master
module, contains the status / control byte and one empty byte.
Subsequently the mailbox data are mapped, when the mailbox is permanently
superimposed (Mode 1).
In the operating mode with suppressable mailbox (Mode 2), the mailbox and
the cyclical process data are mapped next.
The following words contain the remaining process data.
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
Byte Destination
Offset
High Byte
0
-
1
D1
2
D3
3
D5
...
...
max. 23
D45
Process Data Architecture for MODBUS/TCP
Input and Output Process Image
Low Byte
C0/S0
D0
D2
D4
...
D44
I/O Modules
Remark
not used
Control/Status
Mailbox (0, 3, 5, 6 or 9 words) /
Process data (0-16 words)
• 229
byte

Advertisement

Table of Contents
loading

This manual is also suitable for:

I/o system 750

Table of Contents