I/O Modules
Process Data Architecture for EtherNet/IP
The specialty modules represent 1x6 bytes input and output data and seize 1
Instance in Class (0x67) and 1 Instance in Class (0x68).
Data Exchange Module
750-654, (and the variation /000-001)
The Data Exchange modules have a total of 4 bytes of user data in both the
Input and Output Process Image. The following tables illustrate the Input and
Output Process Image, which has a total of 2 words mapped into each image.
Word alignment is applied.
The specialty modules represent 2x2 bytes input and output data and seize 2
Instances in Class (0x67) and 2 Instances in Class (0x68).
SSI Transmitter Interface Modules
750-630, (and all variations)
The above SSI Transmitter Interface modules have a total of 4 bytes of user
data in the Input Process Image, which has 2 words mapped into the image.
Word alignment is applied.
The specialty modules represent 2x2 bytes input data and seize 2 Instances in
Class (0x67).
Input and Output Process Image
Byte Destination
Offset
High Byte
0
D0
1
D2
2
D4
Byte Destination
Offset
High Byte
0
D1
1
D3
Byte Destination
Offset
High Byte
0
D1
1
D3
Low Byte
C/S
Data byte
D1
D3
Input and Output Process Image
Low Byte
D0
D2
Input Process Image
Low Byte
D0
D2
Remark
Control/Status byte
Data bytes
Remark
Data bytes
Remark
Data bytes
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP