7 PARAMETER RANGE AND DEFINITION

7.1 PARAMETER CONTENT AND RANGE

No.
Item
Battery Over Voltage
1
Alarm Threshold
Battery Under Voltage
2
Alarm Threshold
Manually
Set
3
Period
Sensor
1
4
Selection
5
Sensor 1 Open Circuit
Sensor 1 High Alarm
6
Threshold Value
Sensor 1 Control Fan
7
Groups
Sensor
1
8
Curve
Sensor 1 Fan Control
9
Curve
Return
Difference
10
Value of Sensor 1
Sensor
2
11
Selection
12
Sensor 2 Open Circuit
Sensor 2 High Alarm
13
Threshold Value
Sensor 2 Control Fan
14
Groups
Sensor
2
15
Curve
Sensor 2 Fan Control
16
Curve
HFC6100LT Fan Controller User Manual
Table 7 – Parameter Content and Range
Range
(12.0-40.0)V
(4.0-30.0)V
PWM
(0-100)%
Curve
(0-15)
(0-1)
(0-300)℃
(0-5)
Custom
Custom
temperature
Temperature).
Custom fan control curve (X: Temperature
output)
(0-300)℃
Curve
(0-15)
(0-1)
(0-300)℃
(0-5)
Custom
Custom
temperature
Temperature).
Custom fan control curve (X: Temperature
output)
Default
When battery voltage is higher than this
33.0
value and lasts for 20s, controller will
send battery high voltage alarm signal.
When battery voltage is lower than this
8.0
value and lasts for 20s, controller will
send battery low voltage alarm signal.
Manual fan speed mode, press speed-up
10
or speed-down key, the PWM period will
be adjusted.
10
PT100, refer to Table 8.
0
0: Inactive 1: Alarm
When the temperature of external temp.
sensor is higher than this value, it will
95
send high temperature signal. When the
setting value is equal to 300, it will not
send the signal.
1
1 group of fan controlled.
sensor
curve
During the fan output control process,
5
temperature difference required when the
fan output is turned off.
10
PT100, refer to Table 8.
0
0: Inactive 1: Alarm
When the temperature of external temp.
sensor is higher than this value, it will
95
send high temperature signal. When the
setting value is equal to 300, it will not
send the signal.
2
2 groups of fan controlled.
sensor
curve
Remark
(X:
Resistance
Y: Number of fan
(X:
Resistance
Y: Number of fan
Page 13 of 24