7.1 PARAMETER CONTENTS AND RANGE (TABLE 1)

No
Items
Mains
Normal
1
Delay
Mains
Abnormal
2
Delay
Mains
Under
3
Voltage
Mains
4
Voltage
Transfer
5
Delay
6
Start Delay
7
Stop Delay
8
Start Attempts
9
Preheat Time
10
Cranking Time
11
Crank Rest Time
HGM400 Series Genset Controller
Range
(0-3600)s
(0-3600)s
(30-620)V
Over
(30-620)V
Rest
(0-99.9)s
(0-3600)s
(0-3600)s
(1-10)times
(0-300)s
(3-60)s
(3-60)s
ISSUE 2015-05-27
HGM400 Series Genset Controller User Manual
Default
10
The time from mains abnormal to
normal
abnormal;
5
(automatic transfer switch).
When mains voltage has fallen
below the set value, Mains Under
Voltage is active. When set the
184
value as 30V, the controller does
not detect under voltage signal.
Back lash: 10V
When
exceeded the set value, Mains
Over Voltage is active. When set
276
the value as 620V, the controller
does not detect over voltage
signal. Back lash: 10V
Interval time from mains switch
off to generator switch on; or
1.0
from generator switch off to
mains switch on.
Time from mains abnormal or
1
remote start signal is active to
start genset.
Time from mains normal or
1
remote start signal is deactivated
to genset stop.
Maximum crank times of crank
attempts.
3
number, controller will send start
failure signal.
Power-on time of heater plug
0
before starter is powered up.
8
Power-on time of starter
The waiting time before second
10
power up when engine start fail.
Version 1.6
Description
or
from
normal
suitable
for
mains
voltage
When
reach
Page 23 of 44
to
ATS