7.2 PROGRAMMABLE OUTPUT 1-5 (TABLE 2)

No
Items
0
Not Used
1
Common Alarm
2
Energized to Stop
3
Idle Control
4
Preheat Control
5
Close Generator
6
Mains Closed
7
Open ATS
8
Raise Speed
9
Drop Speed
10
Generator Run
11
Fuel Pump Control
12
High Speed Control
13
In Auto Mode
14
Fuel Relay Output
15
Generator Excite
Air Cooler Output
16
17
Reserved
HGM400 Series Genset Controller
HGM400 Series Genset Controller User Manual
Output port is deactivated when "Not Used" is selected.
Include all shutdown alarms and warning alarms. When
there is warning alarm only, it is not self-lock; when a
shutdown alarm occurs, it is self-lock until the alarm is
reset.
Suitable for genset with electromagnet and will active
after "stop idle delay". It is deactivated when the "ETS
Solenoid delay" expires.
Used for engine which has idles. Close before starting
and open in warming up delay; Close during stop idle
delay and open when stop is completed.
Close before starting and open before power up;
When close time is 0, it's continuous output.
When close time is 0, it's continuous output.
(HGM410 without)
When close time is 0, it's disabled.
Close when the generator enters into Warming Up
delay (close time: warming up delay) while open when
Aux.
Close when the generator enters into Stop Idle delay/
Energized to Stop delay (close time: Stop Idle delay)
while open when Aux.
Action
when
genset
deactivated when engine speed is lower than the
"crank disconnect speed".
Close when fuel level is lower than the "Fuel Pump On"
value or when low fuel level warning input is active;
Open when fuel level is higher than the "Fuel Pump
Off" and low fuel level warning input is deactivated;
Close when the generator enters into Warming Up
delay while open after cooling delay.
The controller is in automatic mode.
To control fuel relay output.
Output in start period. If there is no generator
frequency during safety running, output for 2 seconds.
Control air cooler to start\stop according to cooler
temperature.
ISSUE 2015-05-27
Description
is
normal
running
Version 1.6
Page 31 of 44