Smartgen HGM400 Series User Manual page 26

Genset controller
Table of Contents

Advertisement

No
Items
29
Low Oil Pressure
30
Low Fuel Level
31
Config. Sensor
Loss
of
Speed
32
Signal
33
Charge Alt Failure
Battery
34
Voltage
Battery
Under
35
Voltage
HGM400 Series Genset Controller
Range
(0-400)kPa
(0-100)%
(80-140)ºC
(0-400)kPa
(0-100)%
(0-20.0)s
(0-30)V
Over
(12-40)V
(4-30)V
ISSUE 2015-05-27
HGM400 Series Genset Controller User Manual
Default
When
the
sensor value falls below this set
value, "Low Oil Pressure" timer is
initiated. Detecting only after
safety on delay has expired. If
103
the set value is 0, low oil
pressure signal will not be sent
(this only concerns pressure
sensor and does not concern low
oil pressure warning signal via
configurable input port)
When the liquid level of the
external sensor falls below the
set value, "Low Fuel Level" timer
10
is initiated. (this only concerns
fuel level sensor and does not
concern low fuel level warning
signal via configurable input port)
Each value correspond to above
98
28 (Temperature sensor), 29 (Oil
103
pressure sensor) and 30 (Level
10
sensor), respectively.
If the set value is 0, only warning
5.0
and
not
generator.
During
running, when alternator D+(WL)
6.0
voltage has fallen below the set
value and remains for 5s, It will
initiate a shutdown alarm signal.
When
battery
exceeds
remains for 20s, It will initiate a
33.0
warning
warning and not to shutdown the
generator.
When battery voltage has fallen
below the set value and remains
8.0
for 20s, It will initiate a warning
alarm signal. Only warning and
not to shutdown the generator.
Version 1.6
Description
external
pressure
to
shutdown
generator
is
normal
voltage
the
set
value
alarm
signal.
Page 26 of 44