No
Items
Aux.
Input
55
Delay
56
Aux. Input 4
Aux.
Input
57
Active
Aux.
Input
58
Delay
59
Power On Mode
60
Module Address
61
Passwords
62
Crank Disconnect
Disconnect
63
Magnetic Pickup
Disconnect
64
Generator Freq
Disconnect
65
Pressure
High Temperature
66
Inhibit
Low Oil Pressure
67
Inhibit
Low Fuel Level
68
Inhibit
HGM400 Series Genset Controller
Range
3
(0-20.0)s
(0-15)
4
(0-1)
4
(0-20.0)s
(0-2)
(1-254)
(0-9999)
(0-5)
(0-3000)RPM 360
(10.0-30.0)Hz 14.0
Oil
(0-400)kPa
(0-1)
(0-1)
(0-1)
ISSUE 2015-05-27
HGM400 Series Genset Controller User Manual
Default
2.0
11
Factory default: Fuel Level Warn
0
Factory default: Close to active
2.0
0: Stop Mode
0
1: Manual Mode
2: Auto Mode
Communication
1
controller.
1234
There
are
disconnecting starter with engine:
Generator Frequency, Magnetic
Pickup,
2
condition can be used alone and
simultaneously to separating the
start motor and genset as soon
as possible.
See
Table 5
When engine speed higher than
the set value, starter will be
disconnected.
When
higher than the set value, starter
will be disconnected.
When generator oil pressure
200
higher than the set value, starter
will be disconnected.
Factory
0
temperature occurs, shutdown
alarm is initiated. Note 1
Factory default: when low oil
0
pressure occurs, shutdown alarm
is initiated. Note 2
Factory default: when low fuel
1
level occurs, shutdown alarm is
initiated. Note 2
Version 1.6
Description
address
3
conditions
Oil
Pressure.
Each
generator
frequency
default:
when
Page 28 of 44
of
of
high