2. Commissioning
2.1.7 Configuration in the Remote Controller operating mode
Configuration of the bus
node Remote Controller
operating mode
2−30
If there is an FEC in your CPX terminal, you can operate the
bus node in the Remote Controller operating mode. The bus
node then occupies 8 input bytes and 8 output bytes. These
are available for the control program in the FEC and to the
PROFINET Master.
1. Ensure that DIL switch 1 of the bus node is in the
Remote Controller position (see section 1.2.2, Tab. 1/1).
2. Ensure that DIL switch 2 is in the ON position (reserved
for future expansions, see Tab. 1/2).
3. Start your configuration and programming software,
e.g. Siemens STEP 7.
4. Open the hardware configuration, here: HW Config.
5. If you change an existing configuration: If necessary,
remove the existing bus nodes and all other (subordi
nate) modules from this CPX terminal configuration.
6. Perform the bus node selection (station selection) with
the CPX remote controller station type (see section
2.1.4 and 1 in Fig. 2/9).
The bus node is thus configured as Remote Controller.
Festo P.BE−CPX−PN IO−EN en 0710NH