2. Commissioning
Festo P.BE−CPX−PN IO−EN en 0710NH
Hardware Configuration
Identifying the CPX terminal in the network (Device Name)
Use the Node flashing test" function in order to identify your
CPX terminal in the network (the LEDs TP1 and TP2 flash
simultaneously). This function helps you with the allocation
of the Device Name. You can also use this function to test
whether there is a logical data connection to the CPX terminal.
1. Start the PROFINET hardware configuration in your
configuration and programming software (e.g. HW Config
in Siemens STEP 7).
2. Start the Assign Device Name" function from the STEP 7
menu: PLC > Ethernet > Assign Device Name.
The Assign Device Name" window is displayed.
3. If the CPX terminal is not displayed, start the refresh of
the display: Click on Update" for this.
The network is searched and the network participants
found are listed (under Available Devices").
4. Select your found CPX terminal in the list (recognisable
e.g. from the MAC−ID) and click on Flashing on".
The LEDs TP1 and TP2 of the bus node at the found
CPX terminal flash for clear identification.
You can assign a device name to the CPX terminal in the
next step. This device name is also stored on the memory
card (provided it is inserted) of the bus node.
5. Enter a device name in the Device Name" field
(e.g. CPX or CPX−01) and confirm the entry by clicking on
Assign Name".
CPX terminal characteristics, station selection and
IP addressing
1. Start the PROFINET hardware configuration in your
configuration and programming software (e.g. HW Config
in Siemens STEP 7).
2−15